KwTallyRunning watts, starting watts, and the number that actually sizes the unit.

What size generator for a 1500 square foot house running all-electric plus an EV charger

1,500 ft², all-electric plus an EV charger
48kW standby generator
36 kW with a load management module — worth pricing before buying the bigger unit
1,500 ft², all-electric plus an EV charger48 kWGenerator size27.4 kWRunning load38.4 kWPeak when the lar…36 kWWith load managem…
Generator size48kW
Running loadeverything on together, steady state27.4kW
Peak when the largest motor startsthis is the number that sizes the machine38.4kW
With load management12 kW smaller — a $200–500 module36kW
What it runsa 40 A charger adds 9,600 W that runs for hoursall-electric plus an EV charger

Notes

  • The starting surge sizes the generator, not the running load. This house draws 27.4 kW steadily, but when the air conditioner or well pump starts, demand spikes to 38.4 kW for a second or two. A generator that cannot swallow that sags, and the sag is what damages motors and drops the whole panel.
  • Surges do not add up, and this is where people overbuy. Two motors almost never start in the same instant, so you size for the largest single surge, not the sum. Adding every appliance's starting watts together produces a number roughly twice what the house needs — and a generator twice the size costs more to buy, more to install, and burns more fuel at part load.
  • A load management module would let a 36 kW unit do this job. It sheds the air conditioner or the water heater for the few seconds another large load starts, so the generator never sees the combined peak. It costs a few hundred dollars against several thousand for the next size up, and it is almost never offered unprompted. Ask about it explicitly.
  • Almost nobody backs up an EV charger, and you probably should not either. A level 2 charger draws 9,600 W for hours — more than the rest of the house combined during an outage. The standard answer is to lock it out on the generator circuit or shed it with load management, and charge when the power is back. Sizing a standby generator around it is how a house ends up quoted for 48 kW.
  • 48 kW is past ordinary residential standby equipment, which mostly stops around 26 kW. A number this size is a signal that the load list is too ambitious rather than that you need a light-commercial machine: shed the largest loads and the answer comes back into the normal range.
  • A soft starter on the air conditioner is the other lever. It cuts compressor inrush by roughly two thirds for a couple of hundred dollars, and on a house whose peak is set by the AC that frequently drops the generator a whole size.
  • Fuel matters more than the nameplate for a long outage. Natural gas runs indefinitely but delivers roughly 10% less output than propane. Propane means a tank, and a 500-gallon tank at half load runs a 20 kW unit somewhere around two to three days — not the week people assume.
  • The transfer switch is a separate decision and a separate price. A whole-house automatic switch costs more than an essential-circuits one, and it is what determines whether you choose loads in advance or the generator carries everything. Budget it alongside the machine rather than discovering it in the quote.

48 kW, and the surge is what decided it

The house draws 27.4 kW steadily. When the largest motor starts, demand spikes to 38.4 kW for a second or two, and a generator that cannot swallow that sags — which is what damages motors and drops the whole panel.

Surges do not add up

Two motors essentially never start in the same instant, so you size for the largest single surge rather than the sum of all of them. Adding every appliance's starting watts together produces a number roughly twice what the house needs, and a generator twice the size costs more to buy, more to install, and burns more fuel sitting at part load.

Load management is the cheapest kilowatt you will ever buy

A shed module drops the air conditioner or the water heater for the few seconds another large load starts, so the generator never sees the combined peak. Here that is the difference between 48 kW and 36 kW — a few hundred dollars against several thousand.

It is almost never offered unprompted. Ask about it by name.

A soft starter is the other lever

On a house whose peak is set by the air conditioner, a soft starter cuts compressor inrush by roughly two thirds for a couple of hundred dollars, and that frequently drops the generator a whole size on its own.

Fuel changes what "runs" means

Natural gas runs indefinitely and delivers about 10% less output than propane. Propane needs a tank, and a 500-gallon tank at half load runs a 20 kW unit somewhere around two to three days — not the week most people assume when they buy it.